Home » Discover » Controllers » EC100

EC100

  • 4 Universal Inputs (0-5V, dry contact or thermistor)
  • 1 Analog Input (0-5V, 0-10V)
  • 5 Digital Outputs (Triac)

The Smart I/O™ EC100 is a fully programmable controller allowing a complete sequence of operation customization for today’s ever-changing control strategies that are required to meet continued energy efficiency requirements. The reliable cost effective I/O is continuously monitored and precisely controlled by a microprocessor for exceptional performance. To eliminate memory constraints caused by today’s complex applications, as an option, the EC100 can be specified with selectable FLASH/SRAM memory. Communication for monitoring, control and diagnostics is achieved utilizing a LonTalk® TP/FT-10 network with a simple twisted-pair, un-polarized cable. The EC100 can be utilized in many custom or fixed distributed control applications.

The five universal inputs (UI) can be configured in a variety of ways. Universal inputs 1through 4 (UI1-UI4) can interface with resistive type sensors for temperature measurements. These four inputs can also measure 0-5 volts from typical low output resistance sensors. Universal inputs 1 through 4 are also well suited for reading digital inputs and dry contacts for status or alarm conditions. Universal input 5 (UI5) is specifically set-up to measure only voltage. The default voltage range is 0-5 volts and can be set to measure 0-10 volts with the change of an option jumper. The UI’s are well suited to measure voltage values from humidity and many other transducer output signals.

With 12-bits of resolution, the universal inputs are field adaptable and accurate for many types of measurements. The five digital outputs (DO) are Triac outputs for control of additional on/off or pulsed external devices where the current does not exceed 1A at 24 VAC.

The EC100 controller is protected from reverse power supply input wiring, over-voltages, transients, and other common events that can damage unprotected inputs and outputs. User defined algorithms and functions can be programmed using VisualControlÔ, NodeBuilder, LonBuilder or other third party LONWORKS programming tools. The application program can be downloaded over the free topology network and is stored in non-volatile memory so it is retained even after loss of power. The versatile I/O allows numerous applications to be development and implemented with the EC100.

The enclosure snaps right onto a 35mm DIN-rail for quick and easy mounting. Its spring-loaded latching mechanism makes it easy to remove. The wide operating temperature range, -20 to 70 °C, makes the EC100XP well suited for many demanding applications.

General

Communication: LONTALK Protocol
Transceiver: FTT-10, Free Topology
Processor: Neuron 3150 @ 10 MHz
Memory: 56K bytes FLASH, 2K bytes SRAM (Neuron), 24K bytes SRAM (External)*, 0.5K bytes EEPROM (Neuron)

Power

Nominal Input Voltage: 24 VAC
Input Voltage Range: 21-28 VAC
Maximum Consumption: 6 VA, does not include Triac loading

Environmental

Operating Temperature: -20 °C to +70 °C, -4 °F to 158 °F
Storage Temperature: -40 °C to +70 °C, -40 °F to 1 58 °F
Relative Humidity: 5% to 95% (non-condensing)

Warranty

Period: 2 Years (Limited)

Inputs

Number: 5

UI1-UI4

Voltage: 0-5 Volts
Thermistor: Type 2, 3: 10Kohms, (25°C, 77°F)
Digital: Dry Contact

UI5 Only

Voltage: 0-5 Volts, 0-10 Volts (Option Jumper)

All Inputs

Resolution: 12 bits
Accuracy: ±1% FS (25°C, 77°F)
Protection Circuitry: Transient Voltage, ESD

Outputs

Number: 5
5- Digital: Triac 1.0 A @ 24 VAC, Voltage Sourcing
Protection Circuitry: Transient Voltage, ESD

Enclosure

Dimensions: L 105 x W 86 x H 58 mm, (4.13” x 3.39” x 2.28”)
Cover: Lexan 940, UL94-V0 rated
Base: Noryl VO1550, UL94-V0 rated

*Optional – Only available on models with “M” option

EC100 – Model B

Standard 56K flash memory only

EC100 – Model M

Selectable memory (flash, SRAM)

Address

10000 St Clair Avenue

Fairview Heights, IL 62208

Phone

(618) 394-0300